Theben theRonda P360 KNX UP

THE2089000C
Available for 3-5 working days Delivery
£151.50
Details


• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)
• KNX Passive infrared presence detector for ceiling mounting
• Round detection area 360°, up to Ø 24 m (452 m2)
• 2 channel light and 2 channel presence
• 2 channel light C1, C2 with 1 light measurement
• 2 presence channels can be parametrized individually
• Adaptable 1 channel light measurement
• Mixed light measurement suitable for LEDs, fluorescent lamps (FL/PL/ESL) and halogen/incandescent lamps
• Can be used as fully or semi-automatic, switchable
• Switch or constant light control mode with stand-by function
• Dimmable lighting in switch mode with stand-by function
• Brightness switching value or set point value can be set in lux using parameters, on the device itself or via remote control
• Teaching in of the brightness switching value or the set point value
• Room correction factor setting for ¬brightness measurement calibration
• Light time delay can be set using parameters, on the device itself or via remote control
• Switch on delay and time delay ¬for presence can be set
• Detection sensitivity can be set
• Reduced time delay in the event of a shorter stay in the room (short presence)
• Scenario functions
• Test mode for checking function and detection range
• Sensitivity adjustable
• Detection area can be limited using cover clip
• Manual override using telegram or remote control
• Parallel switching of several detectors in Master/Slave or Master/Master possible
• Ceiling installation in flush-mounted socket
• Ceiling installation also possible with surface-mounted frame
• User remote control and management-remote control (optional)
Technical Data
Operating voltage KNX: Bus voltage
Installation height: 2 – 10 m
Minimum height: > 1,7 m
Setting range brightness: 30 – 3000 lx
Detection angle: 360°
Type of connection: KNX bus terminal
Installation type: Ceiling installation
Light switch-off delay: 30 s – 60 min
Lamps: Energy saving lamps, fluorescent lamps, Incandescent/halogen lamps, LEDs
Light measurement: Mixed light measurement
Presence switch-off delay: 10 s - 120 min
Switch-on delay presence: 10 s – 30 min / inactive
Ambient temperature: -15 °C … +50 °C
Type of protection: IP 54 (when fitted)


More Information
More Information
SKU THE2089000C
Color White
Manufacturer Theben
Manufacturers Reference Theben
Type Presence Detector
Medium KNX TP
Installation Ceiling Mounted